SPECIFICATIONS |
USP 600 CON |
Capacity (Pf = 0.8) |
600 VA (480 W) |
INPUT |
Input voltage for utility operation |
-20% to + 15% of nominal input voltage |
Nominal input |
220 Vac single phase, 50 or 60 Hz ± 6% (auto sensing) |
OUTPUT |
Voltage (on battery) |
Pure sine wave at nominal input voltage ± 1% |
Frequency (on battery) |
50 / 60 Hz ± 0.1% (pure sine wave THD < 3%) |
Voltage (AVR) |
Nominal ± 5% |
Automatic voltage stabilizer |
Buck / Double Boost |
Transfer time |
0.5 to 4 msec. |
Overload protection |
On battery - internal current limiting, On line circuit breaker |
SURGE PROTECTION AND FILTERING |
Surge energy rating, peak current capability |
170 Joules, 8 kA x 3 ( L-N, L-G, N-G ) |
Normal mode clamping response time |
Fast Response <25 ns |
Normal mode noise suppression |
Full time EMI / RFI filtering |
Surge energy rating for telephone line |
28.5 Joules, 3.6 kA (RJ45 PIN 4, 5) |
Surge protection for LAN line (10 Base T) |
Yes (RJ45 PIN 1, 2, 3, 6) |
ENVIRONMENTAL |
Ambient operation |
0 - 95% humidity non-condensing, 0 to + 45 °C (32 to 113 °F) |
Ambient storage |
0 - 95% humidity non-condensing, -10 to + 45 °C (14 to 113 °F) |
Audible noise |
< 40 dBA (1 metre) |
PHYSICAL |
Input connector type |
IEC 320 C 14 |
Number of output outlet |
6 |
Maximum dimensions (WxHxD |
17.0 x 25.0 x 50.0 cm. |
Net weight (Approx.) |
13.0 kg. |
Shipping weight (Approx.) |
15.0 kg. |
USER REPLACEABLE BATTERIES |
Rated power |
24 Vdc, Ah rating depend on customer |
Charging current |
10 A or depend on battery Ah rating |
ADVANCE WARNING DIAGNOSTICS |
Front panel LED's |
On-line, Replace battery, Fault, Input voltage level, Battery level, Load level, UPS overload, Main & Intelligent channel fault, Frequency fault, High / Over temperature |
Audible alarms |
On battery, low battery, UPS overload, replace battery, high /over temperat |
COMMUNICATIONS INTERFACE |
DB-9 connector |
Serial interface port can be connected to PC, workstations or servers for automatic unattended shutdown Easy-Mon X may be required |
CONFORMANCE |
Design Regulation |
EN 50091-1, EN 50091-2, EN 55022(B), EN 61000-4-2, (4), (6), IP21 |