TECHNICAL SPECIFICATIONS |
1550 |
Rating (VA/W) |
1550VA/1100W |
Technology |
Tower or Rack 1U |
Technology |
Line-Interactive High Frequency (Pure Sinewave, Booster + Fader) |
Input voltage and frequency ranges without using batteries |
160V-294V (adjustable to 150V-294V) 47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system), 40 Hz in low-sensitivity mode |
Output voltage and frequency |
230 V (+6/-10 %) Adjustable to 200V / 208V / 220V / 230V / 240V), 50/60 Hz +/- 0.1 % (autosensing) |
Input |
1 IEC C14 (10A) |
Outputs Tower model |
8 IEC C13 (10A) |
Outputs Rack 1U model |
6 IEC C13 (10A) |
Typical backup times at 50 and 70% load* |
13/8 mn |
Tower models |
230*150*445mm/15.6kg |
Rack 1U models |
43.2(1U)*438*554mm/19.4kg |
Operating temeprature |
0 to 40°C |
Noise level |
<40dB |
Battery management |
ABM® & Temperature compensated charging method (user selectable), Automatic battery test, deep discharge protection |