TECHNICAL SPECIFICATIONS |
2KVA |
Rating (VA/W) |
2kVA/1.6kW |
Format |
Tower |
Electrical Characteristics |
Technology |
Online double conversion |
Input voltage |
208/220/230/240V |
Input voltage range without using batteries |
176-300V without derating (up to 100-300V with derating) |
Output voltage/THDU |
208V*/220V/230V/240V ±1%, THDU: <2% |
Input frequency range |
40Hz-70Hz, 50/60 Hz autoselection |
Efficiency |
Up to 91% in Online mode |
Overload capacity |
105%-130% : 60s, 130%-150% : 10s, >150% : ≥ 300ms |
Connections |
Input |
IEC C14 |
Outputs |
6 x IEC C13 |
Typical backup times at 50% and 75% load** |
9E |
16/10 min |
9E + 1 EBM |
79/48 min |
9E + 4 EBM |
243/173 min |
Communication |
Communication ports |
1 USB port + 1 RS232 serial port (USB and RS232 ports cannot be used simultaneously) |
Communication slot |
1 slot for Network M2, ModBus-MS or Relay-MS cards |
Software |
Eaton IPM Editions Software |
Operating conditions, Standards and Approvals |
Operating temperature |
0 to 40°C |
Noise level |
<37 dB @ typical load |
Safety |
IEC/EN 62040-1 |
EMC, Performance |
IEC/EN 62040-2 |
Approvals |
CE, CB report (TUV) / EA |
Dimensions D x H x W / Weight |
UPS Dimensions (mm) |
399 x 330 x 190 |
UPS Weight (kg) |
22.4 |
EBM dimensions (mm) |
399 x 330 x 190 |
EBM weight (kg) |
35.8 |