SPECIFICATION |
Viper-1000 |
RATED POWER |
1000 VA / 500 Watt |
LOAD APPLICATION |
1 PC* + Printer** |
INPUT |
Input Voltage (single phase) |
220 VAC ± 25% |
Frequency |
50 Hz ± 12% |
OUTPUT |
Voltage stabilizer mode (sine wave) |
220 VAC ± 10% |
Wave form |
Modified sine wave |
Frequency (backup mode) |
50 Hz ± 0.1% (auto sensing) |
PROTECTION |
Over voltage |
Mains to UPS backup 220 VAC + 25% |
Under voltage |
Mains to UPS backup 220 VAC - 25% |
Transfer time |
2 - 4 msec. (in phase transfer) |
Output short circuit |
Auto cutt-off with audible & visual alarm |
Overload |
Stabilizer mode : Fuse protection or circuit breaker
Backup mode : Short circuit protection
|
Surge energy dissipation |
STD. UL1449 : 76 Joules (Ic = 4500 A) |
Power dissipation |
1,000,000 W within 100 microsec. |
Surge & Noise |
Yes |
Acoustic noise |
Less than 40 dBA at 1 metre |
BATTERY |
Type |
Sealed lead acid (maintenance-free) |
Capacity |
12 V 7 Ah |
Backup time |
15-30 min (depend on load) |
Continuous recharging time |
6-8 hours (80% after fully discharged) |
OUTPUT OUTLET |
Number of backup outlet |
2 |
Number of surge protection outlet |
1 |
FEATURE |
Surge protection for telephone line |
Yes |
Surge protection for laser printer |
Yes |
Automatic no load shutdown |
No |
Automatic restart |
Yes |
Automatic UPS and battery test |
Yes |
Automatic silent alarm sound on power line failure |
Yes |
AC / DC start |
Yes |
INDICATOR ALARM |
LED |
Green : AC mains status
Red : UPS alarm status, etc.
|
AUDIBLE ALARM |
Buzzer |
Line failure, Low battery, UPS test, Short circuit |
ENVIRONMENT |
|
Temperature |
0 - 45 ̊C |
Humidity |
0 - 95% (non-condensing) |
CONFORMANCE |
Design regulation |
EMC category C2 |
PHYSICAL |
Dimension (W x H x D) (cm) |
10 x 16.5 x 30 |
Weight (kg.) |
7.5 |